NF Series Control Panels

Double the technology

Fighting fire power with another powerful element: technology. This is the challenge NITTAN issues with the 3 versions of NF series fire panels: a brand-new family of advanced and performing fire panels, for prevention and safety of medium to large applications, such as those realized in banks, industrial, commercial, and residential buildings.
NF series includes: NF1002 panel: fire panel with 2 conventional zones; NF1004 panel: fire panel with 4 conventional zones; and NF2000 panel that stands out for the possibility of dual configuration: conventional (4 conventional zones expandable up to 12*) and hybrid of conventional and analogue-addressable (4 conventional zones expandable up to 12 and 32 analogue-addressable zones, thanks to the optional NFEXP20 loop module.)
* It will be available in the future to expand to 44 conventional zones with 5 expansion boards.

Multiply the security

NF series panels are available in various versions, can be set up according to the single systems needs, and adopt the dual working mode – conventional and conventional/analogue-addressable – to ensure the most detailed monitoring of fire risks. Moreover, the possibility to integrate several models, make NF panels able to manage up to 1400 detectors.
The most performing panels of the series can control 12 conventional zones and an analogue-addressable loop. The optional EXTING module extends panels functions, covering also the extinguishing system control.

Big things with little effort

In spite of the excellent performance capability, the panels are very easy to set up and operate: the user-friendly interface, with graphic display and LED indicators, allows to operate the system effectively and in a fast and intuitive way. In addition, the USB connection can be used to configure the panel via PC for control and setup parameters, or it is possible to install GSM for sending alarm messages through the GSM mobile network. Available soon, Ethernet modules (optional) enable remote supervision and control of the panels.

Technical Features

Models NF1002 NF1004 NF2000
Conventional Zones 2 zones 4 zones 4 zones
Expandable --- Up to 44 zones
Conventional 12 zones
+ Addressable 32 zones
Connectable detectors 32 per zone
Loop expansion board --- NFEXP20 (optional)
Supported devices --- 254 over Loop
Call point line 1 line
Programmable I/O lines 2 lines 4 lines 4 lines
Supervised outputs 1 supervised output for alarm
Relay outputs 1 relay output for general fault
1 relay output for pre-alarm
2 auxiliary relay outputs
24VDC outputs 1  24VDC output protected by PTC
1  24VDC resettable output protected by PTC
Display Graphic LCD display – Color backlighting
Extinguishing module EXTING (optional)
Event logs Up to 2000 entries
Interfaces and network
MINI-DIN 1 MINI-DIN for configuration with browser
RS-485 Serial lines 2 lines
Remote keypads Up to 2 optional
GSM Optional GSM module
General
Protection Class IP30
Dimensions W320 X H304 X D83 mm W390 X H390 X D99 mm
Weight 4 kg 6 kg
Recommended batteries 12V - 7Ah  12V - 17Ah
Power supply AC230V – +10% / -15%
Power supply unit 2A Max
Output voltage at AL.REL DC27.6V
Available current at AL.REL 650mA Max
Certifications CPR 305/2011, EN54-2, EN54-4, EN54-21, EN12094-1 certification
(CPD 89/106/CEE ex certification)