LP_SPERA Analog Addressable Fire Alarm System

System

Description

Nittan’s UL listed SPERA Series Fire Alarm Control Panels offer modular components for a network system providing a wide variety of applications. Designed for peer-to-peer network communications, the NFU-7000 allows for a maximum of 63 network nodes, while providing reliability, flexibility and expandability.

The NFU-7000 EV protocol is based on the platform which acquired reliabilities in European and Marin markets. Each base panel consists of one driver circuit board which is capable of driving 2 loops. A Nittan EV protocol supports 254 addresses. Owing to the contribution of expandability, addressable detectors and modules are available to be installed without constraint of address numbering. In addition the NFU-7000 equips Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each and a large 16 x 40 back-lit alphanumeric LCD display.
System

Main features

Fire Alarm Control

  • Driver card NK-LDC-3 capable of 2 loops is equipped as standard
  • NFU-7000 has 3 capability of driver card storage (max 6 loops), NFU-7000-L has 7 capability (max 14 loops)
  • One loop supports 254 addresses which can be wired in Class A (Style 6 or 7) or Class B (Style 4)
  • Use of shielded cable is not required for SLC loops
  • Four Class A/B (Style Z/Y) Notification Appliance Circuits rated at 1.7 Amps each
  • One Auxiliary power supply, rated 1.7 Amps at 24VDC in addition to one resettable 4-wire power supply
  • Large 16 line x 40 character Back-lit LCD Display with user friendly menu
  • Correlatable Switch Inputs which allow for multifunctional outputs
  • Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor
  • Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble
  • RS-232 port for remote system printer
  • Two Event History Logs comprised of a 1000 event alarm history log for alarm related events and a 5000 event log for all events
  • Supports three configuration files (current, previous and next configuration) with “hot swap” support
  • Supports Conventional Hardwire Adder Modules
  • Built-in One Man Walk Test operation
  • Provides drift compensation for Photoelectric Smoke Detectors
  • Real time 3D graphical monitoring and control using Nittan’s NFU-Graphic-monitor
  • BACnet support and built-in Ethernet port
  • Supports Boolean logic functions
  • Manual Control Function and Input Simulation Function
  • Multiple group bypass function with built-in false alarm prevention technology

Network Features

  • Up to 63 panels peer-to-peer network communications
  • Mutual surveillance / 2 way control available
  • Class A (Style 6 or 7) or Class B (Style 4) wiring configuration by copper and/or fiber optic network cable
System

System Configration and Specifications

System Configuration

Specifications

NFU-7000NFU-7000-L
Appearance
General
SLC Loops2 loops (Default) expandable up to 6 loops2 loops (Default) expandable up to 14 loops
Addresses per Loop254 addresses per Loop
DisplayLarge 16 by 40 Character Graphic LCD
NetworkMax. 63 fire alarm panels (Copper and/or Fiber Optic Cable)
AnnunciatorsMax. 7 units (LCD type / LED type)
Notification Appliance Circuits4 x 1.7A@24VDC (Class A or B)
4-Wire Power Supply1 x 425mA@22VDC (Resettable)
Auxiliary Power Supply1 x 1.7A@24VDC
Auxiliary Relays3 relays (Common Alarm, Common Supervisory, Common Trouble)
BACnet1 ch (Optional)
Graphic Monitor1 ch (Optional)
Printer1 ch (Optional)
DimensionsH 710 x W 430 x D 146 mmH 950 x W 795 x D 200 mm
Electrical Ratings
AC Line Voltage120V 60Hz / 240V 50Hz, 4 A / 2 A (primary)
Power Supply Ratings12 A max. (secondary)
For Indicating Circus10 A max.
Battery24VDC, Gel-Cell/Sealed Lead-Acid
Charging Capability17-65 AH batteries
Current ConsumptionStanby: 310 mA, Alarm: 733 mA (in default setting, connected devices are not considered)